chameleon 2.0 Programmable Web Server = PWS
Note the MAC address on the label located on the side of the Web server
(insert image)
- Connect laptop and Web server to the same network, use a switch if additional ports are not available
- Open your preferred web browser
- Go to admin.chameleon-cloud.com and find the location you're installing at, the hierarchy is as followed
- Client Name
- Location
- Gateway / Device information
- Select/click on the line containing the "Type" inGate (the line will highlight blue)
- Click on the edit button (it looks like a pencil) just below that same line
- Click into the MAC address field and type in the MAC address collected earlier from the Web server
- To save the MAC address, press the floppy disk icon to the right of the pencil
- After a few minutes click on the reload grid button (it looks like a circle of arrows). If the system is online, the External and Internal IP should appear
- If IP does not appear, close and reopen the admin server
- Open a new tab in the browser and insert the "IP (Internal)" into your browser address line, hit enter
- Click on "Devices"
- IO Control
- In the text box next to "Add Device", input "21", the MODBUS address of the first lighting controller
- Click on "Add Device"
- Ensure the tx: count is going up at a much higher rate then the Err: count.
- Remote Temps, address 1
- In the text box next to "Add Device", input "1". Only one receiver is necessary
- Freezer Controls, addresses 30-42 (currently they need to be addressed in order) Cooler=30 Freezer= 31
- Wattnode Meters, address 50
- Ensure the tx: count is going up at a much higher rate then the Err: count.
- Go to one of the installed thermostats, the first being Kitchen or Back of House preferably
- Press the "Menu" button on the thermostat
- Press and hold the two middle buttons on the thermostat, 3-5 seconds, to get into the Installer Settings
- Scroll down to "Zigbee Install", press "Select"
- When prompted "Add Zigbee thermostat, Yes, No", wait
- Go back to computer and click on "Zigbee"
- Click on "Scan", this will start a 30 second countdown during which the PWS is "looking" for devices to add to the Zigbee network
- Go back to installed thermostats and select "Yes"
- Repeat this process until all thermostats are showing values
- Return to admin.chameleon-cloud.com
- Expand the Gateway line by pressing the "+" associated with that line
- Click on the "Scan" button to add devices to the Web Application
- A new window will open, Add devices as per what has been installed on location
- Press Submit after all installed devices have been selected
- Add zone names by pressing the "+" below the Zones grid
- The Equipment column must have one of the following designations entered exactly
- HVAC
- Lighting
- Refrigeration
- Temperature Monitoring
- Food Probe
- In the equipment column add any of the above names for the Equipment
- In the Zone add the priority of the Equipment, example would be if there is 3 HVAC units, the first unit added would be zone 1. the second would be zone 2, ETC....
- In the zone name, add the name of the equipment. Example Kitchen, Dining
- Repeat process for all added devices
24. Add Energy meter Values.
- go to Admin at top left of page. Open drop down and select Installation Wizard
- Select the site that you are working on from the dropdown list. then press Filter. this will take you to the configuration page
- Expand the energy tab by clicking the "+" sign to the left of Energy.
- once in the Energy window add the CT value to the "Global CT" Box
- Hit Save
25. To add the wireless temperature values follow the same process as above to open the install wizard . once in the install wizard, expand the temperature tab, and in "serial low" add the five digit ID from the back of the device. press the SAVE tab bottom left. continue on for the remaining temperature sensors ID for sensor 1, ID for sensor 2, ETC....
26. When completed exit Install Wizard and return to admin location